In House Oil Analysis Diagnosis

image of wind farms

Transformer Oil Analysis

Analyze the oil at least once a year. Similar to blood picture, which provides information about the health of a patient, the quality of the oil says something about the fitness of the transformer. Decisive factors for good oil quality are, for example, a low water content, a high interfacial tension, a high dielectric strength, and a low power factor. “Dissolved Gas Analysis" (DGA), which examines the ratio of gases dissolved in the oil, is particularly precise.

AGECO International is providing expertise for Root cause analysis and failure remediation & for Diagnosing the transformer ageing process early and reliably based on oil analyses report provided.

AGECO International BENEFITS:
  • Avoiding damage and its consequences

    Insight into the root causes of a failure allows appropriate actions to be taken, avoiding further damage and preventing further unplanned outages.

  • Better reliability, availability and safety

    Addressing the root causes of events and proposing remedial action improves equipment reliability and availability as well as safety.

AGECO International ADDED VALUE:
  • Independent

    We are independent from equipment manufacturers, providing a service in the interests of asset owners, operators and stakeholders.

  • Valuable experience

    We have more than 35 years of field experience analyzing failure events in power grids and many other industrial sectors worldwide.

Why is it necessary to perform oil analysis on transformers?

In industrial units, if the change of a transformer is not planned, a damage on it can pull a loss of partial or total production from few hours to several months depending on the impacted transformer.

A regular follow-up of the state of the oil contained in your transformers thus represents a major interest in your program of maintenance. Indeed, the oil of transformer plays a key role in the proper functioning of the transformers. Regularly analysing regularly the oil of transformer allows to reveal anomalies (electric, thermal defects, premature ageing, loss of insulating capacity, etc.).

abstract image of a power transformer

The control of the oil of transformers presents many interesting points:

What is a transformer oil analysis?

A transformer oil analysis is composed of several types of tests to realise a relevant diagnostic.

One of the tests consists to analyse dissolved gases in the oil of transformer. The dissolved gases analyse of insulating liquids is based on the standard IEC 60599. The concentrations give a precise indication on the conditions of functioning of the equipment. So, We can identify the faults such as heatings or electric defects.

image of oil analysis
Dissolved gas analysis:

During the natural aging process of the oil and insulating parts, especially in the case of thermal or electrical failures, cracked gases form, and are dissolved in the oil. The rate of decomposition and the type of gases change during defective operation, which could be a result of thermal overloading and/or electrical faults. Based on the quantity or type of fault gases, the gas increase rates and the proportions between the gases, the type of failure can be deduced.

Partial discharges with lower energy mainly lead to the formation of hydrogen and methane, as well as small quantities of ethane. Thermal overheating results in the pyrolysis of hydrocarbons. In temperatures between 300-700°C ethylene and propylene accompanied by larger quantities of CO and CO2 prevail. Over 700°C mainly ethylene, propylene and hydrogen form, and above 1000°C acetylene are also formed. Electrical discharges (arcs and spark discharges) cause separation of hydrogen and acetylene, as well as methane and ethylene. By thermal-oxidative cellulose degradation, larger quantities of CO and CO2 are formed.

Through DGA mainly slowly developing faults can be detected. The gradual development of gas concentration allows for a trend analysis, which in turn makes it possible to make a prognosis on the lifespan of the transformer. The following failure sources can also be understood by means of DGA:
  • Identification of Hot spots
  • partial discharges and discharges
  • formation of pollution layers on contacts
  • abnormal cellulose degradation
  • localized metal overheating
  • saturation of the transformer oil with air, which can cause the BHR to trip, without a transformer failure
  • Catalytic effect of coatings and other transformer materials
  • The analysis of Buchholz gases gives additional information about the damage - acute or subtle
  • Leaking diverter switch
The following cannot be detected by means of DGA:
  • the fault location
  • acute faults, that develop within seconds or minutes
  • temperatures, that are below 150°C degrees for a long time, e.g. caused by faulty cooling operation and leads to the degradation of the paper and oil.

The maintenance of insulating liquids is based on standard IEC 60422. This standard is valid for oils that are already contained in transformers. For new oil the reference standard is the IEC 60296.

The following oil values are decisive for the regulation of measures:

abstract image of a power transformer
Oil color and appearance:

The color and appearance of transformer oil are useful for comparative evaluation: a quick color darkening or dark oil is a sign of oil ageing. The analyzed oil color is assigned a number ranging from 1 to 8, whereby the level of discoloration is indicated by means of the rising color number.

By analyzing the appearance, undesirable by-products can be detected. Cloudiness or sediment indicate free water, insoluble sludge or dirt particles. If these are present, then also the breakdown voltage and/or the loss factor and eventually also other oil values are out of the norm and measures must be taken.

Breakdown voltage:

The breakdown voltage indicates how well insulating oil can withstand an electrical load and is therefore decisive for the operational efficiency of a transformer. The breakdown voltage is measured according to the standard IEC 60156. The initial measures to be taken in case of a drop below the insulation voltage limit values of the relative transformer type, depend on the values of the other characteristic oil values.

Water content:

Water formation is caused by the ageing of cellulose- insulating material (paper, pressboard, laminated wood), ageing of oil and infiltration of humidity from the environment by means of badly maintained air dryers and/or defective sealing systems.

There is an equilibrium between the water content in oil and the moisture content in the solid insulation, it reduces the breakdown voltage and accelerates the ageing process. This equilibrium though, is temperature and time-dependent.

As there is never an even temperature in an operating transformer, oil temperature in the tank is much higher at the top than at the bottom, and the same counts for the temperature distribution in the windings - the moisture distribution curves are only a rough estimate. In the moisture distribution curves the water content in the oil can theoretically be distinguished from the moisture content in the cellulose, based on the temperature. This is however valid only for insulation paper and not for pressboard and laminated wood. A precondition is constant temperature and a set equilibrium.

Neutralization value (acidity):

Through progressive ageing (Oxidation) of the oil, polar decomposition products develop. These deteriorate the dielectric properties of the oil. The result of far advanced oil ageing is sludge formation. Sludge greatly compromises the windings because it leads to the formation of sediments, which prevent heat removal. This heat accumulation in turn causes the winding paper to age intensely. A timely diagnosis of the incipient acid formation is therefore important, so that timely counteractive measures can be initiated.

Dieilectric dissipation factor:

The dielectric dissipation factor of an insulating material is the tangent of the dielectric loss angle.

The dielectric loss angle, is the angle in which the phase difference between the applied voltage and consequential current diverges from π/2 rad, when the capacitor's dielectric comprises only of insulating material.

A rising dissipation factor is an indication of oil ageing or oil contamination. The dissipation factor is strongly influenced by polar components and is therefore a very sensitive parameter.

Interfacial tension:

In addition to the neutralization value and the dissipation factor, interfacial tension is another indicator of sludge formation in the transformer. This test measures the concentration of polar molecules in oil, which form during the ageing process. The higher the concentration, the lower the interfacial tension and the likelier it is for the insulating oil to form sludge.

Inhibitor content:

Inhibitors are age protecting agents which delay the decomposition of the insulating oil. The IEC 60296 accredited inhibitor DBPC (Di-tertiary-butyl-para-cresol), with a weight percentage of 0.25 ± 0.040 , is used. Inhibited oils are preferred for transformers > 200 MVA, for heavily loaded transformers such as traction transformers, for oven transformers or at special customer request.
When the accelerated oil ageing process is caused by a transformer malfunction, the original inhibitor content (0,3), can be restored by adding a calculated amount of DBPC in powder form, once the failure has been fixed. Even in the case of normal DBPC- deterioration, the oil can be re-inhibited, although an oil change would be less expensive. This decision can be made only based on the results of the other oil value tests: if these are normal then a re-inhibition can be successful.

Degree of Polymerization (DP and Furan Analysis):

The decomposition of paper is caused by the processes of hydrolysis, pyrolysis and oxidation. The degree of polymerization (DP-value) of paper was defined by the standard IEC 60450 and it counts the number of polymerized glucose rings. During the paper decomposition, the DP-value is reduced and the tensile strength decreases. New cellulose has a DP-value of 1000-1100, aged cellulose on the other hand has a value of only 150-200, which means the end of the transformer's lifespan.

As it is not possible to take paper samples during running operation, the condition of the solid insulation is estimated based on the cellulose decomposition products (2- Furfural). For this purpose a regular trend analysis is necessary.

The furan content in oil depends on:
  • Oil temperature
  • Neutralization value
  • Sludge content
  • Oil/paper ratio
  • Type of oil (inhibited, non-inhibited)
  • Type of paper (thermostabilized, non thermostabilized)

An exact link between the furan content and DP-value cannot be deduced at present. However it is possible to make a trend analysis: based on the change of the furan content, information about thermal conduct of the solid insulation over the years can be obtained.

What is the periodicity recommended to analyse oil of transformer?

The monitoring frequencies defined below are based on more than 35 years of experience and on the recommendations of the standard CEI 60422. Theses frequencies depend on the category and on the age of the transformer :

Property
Color and appearance
Breakdown voltage
Water content
Acidity (neutralization value)
Dielectric dissipation factor (DDF) and resistivity
Inhibitor content
Sediment sludge
Interfacial tension (IFT)
Particles (counting and sizing)
Oxidation stability
Flash point
Compatibilty
Pour point
Density
Viscocity
Polychlorinated byphenyls (PCBs)
Corrosive sulphur
Dibenzyl disufide (DBDS) content
Passivator content
Furan
Polylerization degree
Dissolved gas analysis
Group Transformer Strategic
1 Routine tests 3 years
1 Routine tests 1 year
1 Routine tests 1 year
1 Routine tests 3 years
1 Routine tests 1 year
1 Routine tests 3 years
2 Complementary test 3 years
2 Complementaty test 1 year
2 Complementary test
3 Special investigative tests 3 years
3 Special investigative tests
3 Special investigative tests
3 Special investigative tests
3 Special investigative tests
3 Special investigation tests 3 years
3 Special investigation tests 5 years
3 Special investigation tests 3 years
3 Special investigation tests 3 years
3 Special investigation tests 3 years
3 Speical investigation tests 3 years
3 Special investigation tests 3 years
3 Special investigation tests 1 year
Property
Color and appearance
Breakdown voltage
Water content
Acidity (neutralization value)
Dielectric dissipation factor (DDF) and resistivity
Inhibitor content
Sediment sludge
Interfacial tension (IFT)
Particles (counting and sizing)
Oxidation stability
Flash point
Compatibilty
Pour point
Density
Viscocity
Polychlorinated byphenyls (PCBs)
Corrosive sulphur
Dibenzyl disufide (DBDS) content
Passivator content
Furan
Polylerization degree
Dissolved gas analysis
Group New Transformer Transformer < 15 years Transformer > 15 years Recommended by IEC 60422
1 Routine tests 1 year 5 years 3 years 1 - 2 years
1 Routine tests 1 year 1 year 1 year
1 Routine tests 1 year 1 year 1 year
1 Routine tests 1 year 5 years 3 years
1 Routine tests 1 year 1 year 1 year
1 Routine tests 1 year 5 years 3 years
2 Complementary test 5 years 3 years
2 Complementaty test 1 year 1 year 1 year
2 Complementary test 5 years 3 years
3 Special investigative tests 1 year 5 years 3 years
3 Special investigative tests
3 Special investigative tests
3 Special investigative tests
3 Special investigative tests
3 Special investigation tests 1 year 5 years 3 years
3 Special investigation tests 1 year 5 years 5 years
3 Special investigation tests 1 year 5 years 3 years
3 Special investigation tests 1 year 5 years 3 years
3 Special investigation tests 5 years 3 years
3 Speical investigation tests 5 years 3 years
3 Special investigation tests 5 years 3 years
3 Special investigation tests 1 year 1 year 1 year
Property
Color and appearance
Breakdown voltage
Water content
Acidity (neutralization value)
Dielectric dissipation factor (DDF) and resistivity
Inhibitor content
Sediment sludge
Interfacial tension (IFT)
Particles (counting and sizing)
Oxidation stability
Flash point
Compatibilty
Pour point
Density
Viscocity
Polychlorinated byphenyls (PCBs)
Corrosive sulphur
Dibenzyl disufide (DBDS) content
Passivator content
Furan
Polylerization degree
Dissolved gas analysis
Groups New Transformer Transformer < 15 years Transformer > 15 years Recommended by IEC 60422
1 Routine tests 1 year 5 years 3 years 1 - 3 years
1 Routine tests 1 year 1 year 1 year
1 Routine tests 1 year 1 year 1 year
1 Routine tests 1 year 5 years 3 years
1 Routine tests 1 year 1 year 1 year
1 Routine tests 1 year 5 years 3 years
2 Complementary test 5 years 3 years
2 Complementaty test 1 year 1 year 1 year
2 Complementary test 5 years 3 years
3 Special investigative tests 1 year 5 years 3 years
3 Special investigative tests
3 Special investigative tests
3 Special investigative tests
3 Special investigative tests
3 Special investigation tests 1 year 5 years 3 years
3 Special investigation tests 1 year 5 years 5 years
3 Special investigation tests 1 year 5 years 3 years
3 Special investigation tests 1 year 5 years 3 years
3 Special investigation tests 5 years 3 years
3 Speical investigation tests 5 years 3 years
3 Special investigation tests 5 years 3 years
3 Special investigation tests 1 year 1 year 1 year
Property
Color and appearance
Breakdown voltage
Water content
Acidity (neutralization value)
Dielectric dissipation factor (DDF) and resistivity
Inhibitor content
Sediment sludge
Interfacial tension (IFT)
Particles (counting and sizing)
Oxidation stability
Flash point
Compatibilty
Pour point
Density
Viscocity
Polychlorinated byphenyls (PCBs)
Corrosive sulphur
Dibenzyl disufide (DBDS) content
Passivator content
Furan
Polylerization degree
Dissolved gas analysis
Group New Transformer Transformer < 15 years Transformer > 15 years Recommended by IEC 60422
1 Routine tests 1 year 5 years 3 years 1 - 4 years
1 Routine tests 1 year 1 year 1 year
1 Routine tests 1 year 1 year 1 year
1 Routine tests 1 year 5 years 3 years
1 Routine tests 1 year 1 year 1 year
1 Routine tests 1 year 5 years 3 years
2 Complementary test 5 years 3 years
2 Complementaty test 1 year 1 year 1 year
2 Complementary test 5 years 3 years
3 Special investigative tests 1 year 5 years 3 years
3 Special investigative tests
3 Special investigative tests
3 Special investigative tests
3 Special investigative tests
3 Special investigation tests 1 year 5 years 3 years
3 Special investigation tests 1 year 5 years 5 years
3 Special investigation tests 1 year 5 years 3 years
3 Special investigation tests 1 year 5 years 3 years
3 Special investigation tests 5 years 3 years
3 Speical investigation tests 5 years 3 years
3 Special investigation tests 5 years 3 years
3 Special investigation tests 1 year 1 year 1 year
Property
Color and appearance
Breakdown voltage
Water content
Acidity (neutralization value)
Dielectric dissipation factor (DDF) and resistivity
Inhibitor content
Sediment sludge
Interfacial tension (IFT)
Particles (counting and sizing)
Oxidation stability
Flash point
Compatibilty
Pour point
Density
Viscocity
Polychlorinated byphenyls (PCBs)
Corrosive sulphur
Dibenzyl disufide (DBDS) content
Passivator content
Furan
Polylerization degree
Dissolved gas analysis
Group New Transformer Transformer < 15 years Transformer > 15 years Recommended by IEC 60422
1 Routine tests 5 years 5 years 2 - 6 years
1 Routine tests 2 years 2 years 2 years
1 Routine tests 2 years 2 years 2 years
1 Routine tests 2 years 5 years 5 years
1 Routine tests 2 years 2 years 2 years
1 Routine tests
2 Complementary test
2 Complementaty test
2 Complementary test
3 Special investigative tests
3 Special investigative tests
3 Special investigative tests
3 Special investigative tests
3 Special investigative tests
3 Special investigation tests
3 Special investigation tests 2 years 5 years 5 years
3 Special investigation tests
3 Special investigation tests
3 Special investigation tests
3 Speical investigation tests
3 Special investigation tests
3 Special investigation tests 2 years 2 years 2 years
Property
Color and appearance
Breakdown voltage
Water content
Acidity (neutralization value)
Dielectric dissipation factor (DDF) and resistivity
Inhibitor content
Sediment sludge
Interfacial tension (IFT)
Particles (counting and sizing)
Oxidation stability
Flash point
Compatibilty
Pour point
Density
Viscocity
Polychlorinated byphenyls (PCBs)
Corrosive sulphur
Dibenzyl disufide (DBDS) content
Passivator content
Furan
Polylerization degree
Dissolved gas analysis
Group Transformer Strategic
1 Routine tests
1 Routine tests 2 years
1 Routine tests 2 years
1 Routine tests 2 years
1 Routine tests 2 years
1 Routine tests 2 years
2 Complementary test
2 Complementaty test
2 Complementary test
3 Special investigative tests
3 Special investigative tests
3 Special investigative tests
3 Special investigative tests
3 Special investigative tests
3 Special investigation tests
3 Special investigation tests
3 Special investigation tests
3 Special investigation tests
3 Special investigation tests
3 Speical investigation tests
3 Special investigation tests
3 Special investigation tests

Note:
The above table is valid for consistent trending data, in case of abnormality detected with the results, intervals for making oil analysis will be reviewed to suit the investigation.

Interpretation of Dissolved Gas Analysis

(Diagnosis based on IEC 60599)

We can offer to you the possibility to assess the dissolved analysis results through our platform by entering your gaz values in the table below.

For any fault detected in your Transformer / Reactor / OLTC we recommend you to contact us for further investigation and an action for repair.

Enter your Gas Concentration in ppm

Duval Triangle Diagnosis

Note:
  • Triangle 1 is used first for basic and single fault. If further information is needed, Triangle 4 and 5 can be used.
  • Triangle 2 is applied to conventional, compartment OLTC where normal operation involves mostly arc breaking in oil.
  • Triangle 4 & 5 should never be used for faults identified first with Triangle 1 as electrical faults D1 or D2.

Duval Triangle 1

Power & Distribution Transformer:

  • Mineral Oil
  • Typical Fault

For PD, T1 and T2 check Duval Triangle 4, For T2 and T3 check Duval Triangle 5.

Input your values below:

ppm
ppm
ppm

Diagnosis Results:

Get in touch for further investigation by our experts

Duval Triangle 2

On Load Tap Changer (Standard):

  • Mineral Oil
  • Standard Faults

Input your values below:

ppm
ppm
ppm

Diagnosis Results:

Get in touch for further investigation by our experts

Duval Triangle 3

Power & Distribution Transformer:

  • Bio Temp Oil
  • Standard Faults

Input your values below:

ppm
ppm
ppm

Diagnosis Results:

Get in touch for further investigation by our experts

Duval Triangle 3

Power & Distribution Transformer:

  • FR3 Oil
  • Standard Faults

For PD, T1 or T2 check Duval Triangle 6 & 7

Input your values below:

ppm
ppm
ppm

Diagnosis Results:

Get in touch for further investigation by our experts

Duval Triangle 2 Type 2a

On Load Tap Changer (MR OilTaps® M & D):

  • Mineral Oil
  • Standard Faults

Input your values below:

ppm
ppm
ppm

Diagnosis Results:

Get in touch for further investigation by our experts

Duval Triangle 6

Power & Distribution Transformer:

  • FR3 Oil
  • Low Energy Faults

With PD, T1, or T2 (Triangle 3 FR3) / DO NOT USE for T3, D1, D2 and DT

Input your values below:

ppm
ppm
ppm

Diagnosis Results:

Get in touch for further investigation by our experts

Duval Triangle 2 Type 2b

On Load Taps Changer (MR VacumTaps® VR) :

  • Mineral Oil
  • Standard Faults

Input your values below:

ppm
ppm
ppm

Diagnosis Results:

Get in touch for further investigation by our experts

Duval Triangle 2 Type 2c

On Load Taps Changer (MR VacumTaps® VV) :

  • Mineral Oil
  • Standard Faults

Input your values below:

ppm
ppm
ppm

Diagnosis Results:

Get in touch for further investigation by our experts

Duval Triangle 2 Type 2d

On Load Taps Changer (OilTaps® R & V):

  • Mineral Oil
  • Standard Faults

Input your values below:

ppm
ppm
ppm

Diagnosis Results:

Get in touch for further investigation by our experts

Duval Triangle 2 Type 2e

On Load Taps Changer (MR OilTaps®; G; ABB few UZD®; some UZB®):

  • Mineral Oil
  • Standard Faults

Input your values below:

ppm
ppm
ppm

Diagnosis Results:

Get in touch for further investigation by our experts

Duval Triangle 3

Power & Distribution Transformer:

  • MIDEL Oil
  • Standard Faults

Input your values below:

ppm
ppm
ppm

Diagnosis Results:

Get in touch for further investigation by our experts

Duval Triangle 3

Power & Distribution Transformer:

  • Silicone Oil
  • Standard Faults

Input your values below:

ppm
ppm
ppm

Diagnosis Results:

Get in touch for further investigation by our experts

Duval Triangle 4

Power & Distribution Transformer:

  • Mineral Oil
  • Low Energy Faults

For PD, T1 and T2 of Duval Triangle 1 only.

Input your values below:

ppm
ppm
ppm

Diagnosis Results:

Get in touch for further investigation by our experts

Duval Triangle 5

Power & Distribution Transformer:

  • Mineral Oil
  • Low Energy Faults

For T2 and T3 of Duval Triangle 1 only.

Input your values below:

ppm
ppm
ppm

Diagnosis Results:

Get in touch for further investigation by our experts

Duval Triangle 7

Power & Distribution Transformer:

  • FR3 Oil
  • Low Energy Faults

With PD, T1 and T2 (Triangle 3 FR3) / DO NOT USE for T3, D1, D2 an DT.

Input your values below:

ppm
ppm
ppm

Diagnosis Results:

Get in touch for further investigation by our experts